2009 plumbing code pdf




















Piping through concrete or masonry walls shall not be subject to any load from building construction. The plumbing system shall be protected from freezing or overheating. The following conditions shall be met: 1. Water service piping shall be installed below recorded frost lines. Minimum earth cover above the top of building sewers that connect to public sewage systems shall be inches. Minimum earth cover above the top of building sewers that connect to individual sewage disposal systems shall be inches.

In systems that are used seasonally, water piping shall have provisions to be drained. Piping shall be installed so that the contents will not be heated due to close proximity to any heat source or from direct solar radiation.

In areas with seasonal freezing outdoor temperatures, all drain piping and water piping installed in exte- rior walls, attics, and other areas exposed to outdoor temperatures shall be protected from freezing. In heated spaces, the piping shall be installed on the heated side of the building insulation. Such private systems shall meet the standards for installation and use established by the Health Department or other agency having jurisdiction.

See Chapters 16 and Four-inch by three-inch closet bends shall be permitted. In the installation or removal of any part of a drainage or vent system, dead ends shall be avoided. In the installation or removal of any part of a potable water system, dead ends shall be avoided. Food or drink shall not be stored, prepared or displayed beneath overhead drain or vent piping unless such pipes are protected against leakage or condensation reaching the food or drink.

In new or remodeled construction, drain and vent piping shall not be located above food preparation, storage, display, or serving areas where possible. Where drain and vent piping must be installed above such areas, the amount of piping and the number of pipe joints shall be minimized. Drain and vent piping above such areas shall be subjected to a standing water test of not less than 25 feet or 10 psig.

Piping subject to operation at temperatures that may cause condensation on the external surfaces of the pipe shall be thermally insulated to prevent condensation. Materials installed in plumbing systems shall be handled and installed as to avoid damage so that the quality of the material will not be impaired. No defective or damaged materials, equipment or apparatus shall be installed or maintained.

See Sec- tions 2. The marking shall be done during the time of manufacture. Field mark- ing shall not be permitted. Materials not listed in Table 3. Note: Abbreviations in Table 3. General use - 12 oz.

Flashing for vent pipes - 8 oz. Sheet lead shall be not less than the following: a. Shower pans—not less than 4 pounds per square foot psf and be coated with an asphalt paint or equivalent. Flashings of vent terminals—not less than 3 pounds per square foot psf. Shower pans—approved plastic sheeting material.

Cleanout plugs shall be of brass, plastic, stainless steel, or other approved materials and shall have raised or countersunk square heads, except that where raised heads will cause a tripping hazard, countersunk heads shall be used.

Cleanout caps shall be of brass, plastic, reinforced neoprene, cast-iron, or other approved material and shall be readily removable.

If of hard lead, they shall weigh not less than 1 lb. Flanges shall be soldered to lead bends or shall be caulked, soldered, or threaded into other metal. Closet screws and bolts shall be corrosion-resisting. When of brass or copper tube, the material shall be at least 0. See Table 3. See Section Plans for all septic tanks shall be submitted to the Authority Having Jurisdiction for approval. Such plans shall show all dimensions, reinforcing, structural calculations and such other pertinent data as may be required.

Septic tanks shall be constructed of sound durable materials, not subject to excessive corrosion or decay and shall be watertight. See Sections Plastic pip- ing used for hot water distribution shall be installed in accordance with the requirements of Section NOTE: The working pressure rating of certain approved plastic piping materials varies depending on the pipe size, material composition, wall thickness, and methods of joining.

Piping used for domestic water shall be suitable for the maximum temperature, pressure, and velocity that may be encountered, including temporary increases and surges. Materials used in the potable water supply system, including faucets and valves, shall not contain more than 8 percent lead.

Joints shall be watertight and root proof. The Authority Having Jurisdiction may grant a variation to the extent necessary to relieve the undue nature of the hardship. A record, open to the public, shall be kept of each variation granted under this section. The Authority Having Jurisdiction may approve the use of any material or method not expressly conforming to the requirements of this Code provided all of the following conditions are met: 1.

The material or method is not expressly prohibited by this Code. The material or method is determined to be of such design or quality as to appear suitable for the pro- posed use. A record of such approval is kept and shall be available to the public. Such tests shall be made by an approved testing agency at the expense of the applicant.

DWV Fabricated Fittings: 16 3. ASTM D Sanitary Floor Sinks: VI. Suction Systems: VII. CSA 4. Table 3. All burrs on the outside of the pipe and butt ends shall be removed before the installation. Pipe sealing or lubricating compound required for threaded pipe joints shall be applied to the male pipe end only and shall be insoluable and nontoxic.

See Section 2. No paint, varnish, or other coatings shall be permitted on the jointing material until after the joint has been tested and approved. Lead shall be run in one pouring and shall be caulked tight. Thread seal tape, pipe joint compound, or other thread lubricant shall be applied only to the male threads. Joints between lead pipe and cast-iron, steel, or wrought iron shall be made by means of a caulking ferrule, soldering nipple, or bush- ing.

Solder for joints in potable water piping shall contain not more than 0. The joints shall be rated by the manufacturer for not less than psig at deg F. Fittings shall be marked with those tubing materials that they are intended to be used with unless they are suitable for use with all three tubing materials copper, CPVC, and PEX.

Brazed joints in copper tubing shall be made in accordance with accepted industry practice. See Ap- pendix L for an accepted practice for general plumbing. Mechanically formed tee branches shall be permitted in copper tubing in water distribution systems.

The branch connections shall be formed with appropriate tools and joined by brazing. The branch tube end shall be notched and dimpled with two sets of double dimples. The dimples in the branch tube shall be in line with the run of the main.

The joints shall be brazed in accordance with Section 4. Mechanically formed tee branches shall not be permitted in drainage piping. Not more than 25 percent of the annular space shall be used for jute or hemp. Additional mortar of the same composition shall then be applied to form a one to one slope with the barrel of the pipe.

The bell or hub of the pipe shall be left exposed for inspection. When necessary, the interior of the pipe shall be swabbed to remove any mortar or other material that may have found its way into such pipe. The thickness of the weld shall be at least as thick as the lead being joined. Joints in stainless steel DWV systems shall be made with an elastomeric o-ring of a material that is suitable for the intended service. Joints between stainless steel drainage systems and other piping materials shall be made with an ap- proved adapter coupling.

Joints shall be installed in accordance with the manufacturer's instructions. Joints in plastic piping shall be made by one of the following methods where appropriate: 1.

Joints shall be made in accordance with the manufacturer's instructions for the method used. Primers shall be purple in color and solvent cements shall not be purple in color. Solvent cements used with primers shall be orange in color.

Primers where used shall not be orange in color. Slip joints using approved ground joint brass compression rings that allow adjustment of tubing but provide a rigid joint when made up, shall not be considered as slip joints that require access. The complete joint assembly shall be suitable for the intended use and comply with a standard listed in Table 3.

Galvanized steel pipe may be jointed using rolled or cut grooves. Other interior coated pipe shall not be joined using rolled grooves. Field bends shall be made in accordance with Table 4. Bends shall be made only with bending equipment and procedures intended for that purpose. Hard drawn tubing shall not be bent with tubing benders intended for only annealed soft tube. All bends shall be smooth and free from buckling, cracks, and other evidence of mechanical damage.

Table 4. Tube Type Temper Min. Bend Radius, in. Joints from copper tube to threaded pipe shall be made as follows: 1. DWV Systems: with copper or brass threaded adapters.

To any Non-Ferrous Piping: copper or brass threaded adapter. Fittings and couplings for use under this Section shall either 1 comply with a standard listed in Table 3. All metal parts shall be corrosion- resisting. Shielded couplings may be installed above ground or underground, as intended by the manufacturer. Mechanical unshielded couplings using thermoplastic elastomer gaskets shall consist of a rigid or semi- rigid sealing sleeve and corrosion-resisting metal screw clamping bands.

The pipe shall be supported on both sides of the coupling within 18 inches of the centerline of the coupling. Mechanical unshielded couplings using thermo- plastic elastomer gaskets shall be permitted aboveground or underground.

Flexible unshielded couplings shall consist of an elastomeric sealing sleeve and corrosive-resisting metal screw clamping bands. Couplings installed aboveground shall include center stops. Threaded Joints: Threaded joints for connecting plastic drainage piping to other materials shall be made with proper male or female threaded plastic adapters.

Joints shall not be over-tightened. After hand tightening, one-half to one full turn shall be made with a strap wrench. Solid Wall Plastic Pipe to Cast-iron Hub Ends: Joints shall be made by caulking the plastic pipe into the hub end with molten lead and oakum or by use of a compression gasket that is compressed when the plastic pipe is inserted into the hub end.

Joints shall be permitted to be made with or without a hub end plastic adapter. Adapters without a caulking bead shall be permitted. Cellular Core Plastic Pipe to Cast-iron Hub Ends: Joints shall be made by caulking a solid plastic adapter into the cast-iron hub end with molten lead and oakum or by use of a compression gasket that is compressed when the plastic pipe is inserted into the hub end.

Cel- lular core plastic pipe shall not be lead caulked. Transition ce- ment shall not be permitted to be used within buildings. Transition joints shall be a minimum of 3 feet outside of buildings. Connections between drainage piping and wall hung water closets shall be made by means of an approved extension nipple or horn adapter.

Exterior wall openings shall be made watertight. Fixtures shall not be double-trapped unless a relief vent is provided between the two traps. Note: Interceptors in Chapter 6 that do not provide the required trap seal shall be provided with a separate trap. No trap shall be larger than the drainage pipe into which it discharges. Integral traps shall conform to appropriate standards. Solid connections, slip joints, or couplings may be used on the trap inlet, trap outlet, or within the trap seal.

See Section 7. Each build- ing trap when installed shall be provided with a cleanout and with a relieving vent or fresh air intake on the inlet side of the trap that shall be at least one-half the diameter of the drain to which it connects. Such reliev- ing vent or fresh air intake shall be carried above grade and terminate in a screened outlet located outside the building. The following types of traps shall be prohibited: 1. Traps that depend upon moving parts to maintain their seal. Bell traps.

Crown vented traps. Drum traps. Hair interceptors, precious metal interceptors and similar appurtenances shall be permitted as required. Traps that could lose their seal due to evaporation because of infrequent use shall have accessible means to replenish the trap seal or be connected to a trap primer conforming to ASSE or ASSE In addition to the priming requirements of Section 5.

Cleanouts in horizontal drainage lines shall be spaced at intervals not exceeding the following values: 4" pipe size or less: 75 feet 5" size and larger: feet b. The distance referred to in Sections 5. Rain leaders and conductors connected to a building storm sewer shall have a cleanout installed at the base of the outside leader or inside conductor before it connects to the horizontal drain. There shall be a cleanout near the junction of a building drain and building sewer either inside or outside the building wall.

Cleanouts shall be placed in the building sanitary sewer and the building storm sewer at the property line and brought to the surface in accordance with the requirements of the Adopting Agency. Table 5. Manholes shall be provided as cleanouts for building sewers 12" size and larger. Manholes shall be pro- vided at every change of size, alignment, direction, grade, or elevation. The distance between manholes shall not exceed feet.

Manholes may be provided in lieu of cleanouts in underground building sewers, building drains, and branches thereof, 8" size and larger. Such manholes shall comply with the requirements of Section 5. If manholes are installed indoors, they shall have a bolted, gas-tight cover.

Manhole construction shall comply with the standards of the Authority Having Jurisdiction. Cleanouts smaller than 3 inches shall be so installed that there is a 12" clearance for rod- ding. Where it is necessary to conceal a cleanout plug, a covering plate or access door shall be provided that will permit access to the plug. Equipment shall be properly vented if loss of its trap seal is possible. Liquid waste treatment equipment shall be so installed that it is accessible for the removal of covers and the performance of necessary cleaning, servicing and maintenance.

The need to use ladders or move bulky objects in order to service interceptors and other liquid waste treatment equipment shall constitute a violation of accessibility. Grease interceptors shall comply with the requirements of the Adopting Agency. Grease interceptors include the following types: 1. Type I Hydro-mechanical interceptors 2.

Grease removal or recovery devices GRD 3. Type II Gravity interceptors c. Hydro-mechanical interceptors up to gallons per minute capacity shall comply with the performance, testing, and installation requirements of ASME A These interceptors shall be sized according to Section 6. Outdoor underground gravity grease interceptors serving commercial kitchens shall be sized and designed by a registered design professional who is licensed to practice in the particular jurisdiction.

Gravity grease interceptors shall comply with the requirements of the Adopting Agency, including materials of construction, arrangement, minimum size, and retention time. Where food waste grinders discharge through a hydro-mechanical or GRD grease interceptor, a solids separator shall be installed either in the drain line from the food waste grinder or upstream of the grease interceptor to prevent food waste particles from entering the grease interceptor.

Solids separators shall not be required where food waste grinders discharge to a gravity grease interceptor. Commercial dishwashers shall be permitted to discharge through a grease interceptor.

Sinks or sink compartments used for sanitizing pots or other ware shall not be drained through a grease interceptor. All compartments of multi-compartment sinks shall be considered to drain simultaneously, except that sanitizing compartments shall not be drained through a grease interceptor.

Table 6. Such contaminants shall be removed by an ap- propriate separator. Such locations include, but are not limited to, car or truck washing facilities, engine cleaning facilities, and similar operations.

Drains shall not be required in service or repair garages that employ dry absorbent cleaning methods; however, if any drains are located in such areas, they shall discharge to the sanitary sewer through a sand interceptor and oil interceptor. Any storm water shall be drained separately and directly to the storm sewer.

Such drainage, including melting snow, ice or rainwater runoff from vehicles, shall not be connected to the sani- tary sewer. Where oil separators include a waste holding tank, it shall not be used to store or contain any other waste oil e. Field-fabricated oil separators shall have a depth of not less than two feet below the invert of the dis- charge outlet. The outlet opening shall have a water seal depth of not less than 18 inches. Oil separators shall have a 3-inch minimum discharge line and a 2-inch minimum vent to atmosphere.

The discharge line shall have a full-size cleanout extended to grade or otherwise be accessible. Pumps shall be adequately sized, explosion-proof, and accessible. Sand inter- ceptors shall comply with Section 6. A sand interceptor shall be installed upstream from an oil separator if required in Section 6.

A sand interceptor shall be provided downstream from any drain whose discharge may contain sand, sediment, or similar matter on a continuing basis that would tend to settle and obstruct the piping in the drainage system.

The outlet pipe of a sand interceptor shall be the same size as the drain served. The inlet to the interceptor shall be at the same elevation as, or higher than, the outlet. The bottom of the inlet section shall be at least 24 inches below the invert of the outlet pipe. A solid removable cover shall cover the outlet section. A cleanout shall be provided for the outlet line. Solids interceptors shall be provided where necessary to prevent harmful solid materials from entering the drainage system on a continuing basis.

Solids interceptors shall separate solids by gravity, trapping them in a removable bucket or strainer. Neutralizing or dilution tanks shall be provided where necessary to prevent acidic or alkaline waste from entering the building drainage system.

Such waste shall be neutralized or diluted to levels that are safe for the piping in the drainage and sewer systems. Vents for neutralizing or dilution tanks shall be constructed of acid-resistant piping and shall be indepen- dent from sanitary system vents.

No strain shall be transmitted to the connecting piping. Fastening screws or bolts shall be corrosion-resisting. In addition to the wall support brackets, pedestals or legs may provide additional support for pedestal lavatories.

Such access is not required for connections that are sol- dered, threaded, solvent cemented, or equivalently secured. Waterless non-water urinals shall have a liquid trap seal as required by Section 5.

Lavatories shall comply with the following standards: 1. Except as required under Section 7. Public lavatory faucets, other than the metering type, shall be designed and manufactured according to ASME A Metering faucets shall deliver not more than 0. A strainer, pop-up stopper, crossbar grid, or other device shall be provided to protect the waste outlet. Bathtubs shall comply with the following standards: 1. Waste outlets shall be equipped with a pop-up waste, chain and stopper, or other type of drain plug.

Surrounding wall construction shall be in accordance with Section 7. Riser pipes to shower heads shall be secured in accordance with Section 7. The provisions for wet vent- ing in Section The minimum outside rough-in dimension for shower bases and prefabricated shower compartments shall be 32 inches, except where a shower receptor has a minimum overall dimension of 30 inches mm in width and 60 inches 1, mm in length. The walls in shower compartments and above built-in bathtubs having installed shower heads shall be constructed of smooth.

Manufactured shower pans, shower bases, and shower receptors shall be installed in accordance with this Code and the manufacturer's instructions. Sinks shall comply with the following standards: 1. Each compartment in a kitchen sink or bar sink shall have an outlet suitable for either a domestic food waste grinder or a basket strainer.

Service sinks and mop receptors shall have removable strainers and waste outlet connections not less than 2" nominal size. Weep hole drains that form a cross connection between ground water and the potable water supply shall not be permitted. Such units may connect to a kitchen sink drain outlet, as permitted under Section 7. The water supply to dish- washing machines shall be protected from back-siphonage by an integral air gap or other internal means. The discharge line from the dishwasher shall be not less than the size recommended by the dishwasher manufacturer.

The discharge may also drain indirectly into a trapped standpipe, or receptor. Commercial dishwashing machines shall be indirectly connected to the drainage system through either an air gap or an air break. Commercial dishwashers shall be permitted to discharge through a grease interceptor in accordance with Section 6. Where traps are automatically primed, the priming connection shall be above the weir of the trap. Floor drains shall be not less than 2" nominal size. Floor drains shall be installed in the following areas: 1.

Toilet rooms containing either two or more water closets or wall hung urinals or a combination of one or more water closets and wall hung urinals, except in a dwelling unit. Commercial kitchens. Common laundry rooms in commercial buildings and buildings having more than two dwelling units. The water supply connection shall be protected from back-siphonage in accordance with Chapter Examples of such special installations include decorative fountains, ornamental pools, waterfalls, swimming and wading pools, baptisteries, and similar custom-built equipment.

Ballcocks shall be the anti-siphon type and comply with ASSE Flushometer valves shall be accessible for maintenance and repair. Water closets shall be the elongated type with integral or separate seats. Plans for plumbing systems, where required, shall indicate the maximum number of persons to be served by the facilities. In occupancies having established seating, such as auditoriums and restaurants, the number of occupants for plumbing purposes shall not be less than the number of seats.

The lavatories required by Tables 7. Separate toilet facilities shall be provided for each sex. Residential installations. In occupancies serving 15 or fewer people, one toilet facility, designed for use by no more than one person at a time, shall be permitted for use by both sexes.

Drinking Water Facilities: A kitchen or bar sink shall be considered as meeting the requirements for drinking water facilities for employees.

Laundry Trays: Multiple dwelling units or boarding houses without public laundry rooms shall not require laundry trays. Service Sinks: Service sinks may be omitted when the Authority Having Jurisdiction determines that they are not necessary for proper cleaning of the facility. Types of occupancies not shown in Table 7. Where swimming pools operated by an apartment building, condominium, or similar multi-family dwelling unit are restricted to the use of residents and guests of residents of dwelling units in the immedi- ate vicinity of the pool, the minimum required toilet facilities for bathers within the pool compound shall be one 1 male toilet room and one 1 female toilet room, each consisting of a water closet and lavatory as a minimum.

Requirements for customers and employees shall be permitted to be met with a single set of restrooms accessible to both groups. Fixtures for customer use shall be permitted to be met by providing a centrally located facility accessible to several stores. The maximum distance of entry from any store to this facility shall not exceed feet. The maxi- mum distance of entry from any store to this facility shall not exceed feet.

Drinking water facilities are not required for customers where normal occupancy is short term. Food service establishments with an occupant load of or more customers shall be provided with separate toilet facilities for employees and customers. Customer and employee toilet facilities may be combined for customer loads of or less. For employees of 15 or less, one toilet facility, designed for use by no more than one person at a time, shall be permitted for use by both sexes. Drinking water facilities are not required in restaurants or other food service establishments if drinking water service is provided.

Waste discharge from such equipment shall enter the drainage system through an air gap. Types of entrapment can include, but not be limited to, rigid, non-giving protrusions, wedge-shaped openings, and any arrangement of components that could pinch and entrap the user. The suction inlets shall be piped so that water is drawn through the inlets simultaneously by a common suction line to the pump.

Blocking one suction inlet shall not create excessive suction at other suction inlets. The equipment installer shall assemble and install the equipment in accordance with the manufacturer's instructions. See Notes: 4, 14,16 b Prisons, jails and reformatories long term. Moderated hazard. For accessible requirements, see local, state, or national codes. Drinking fountains are not required in restaurants or other food service establishments if drinking water service is available.

Drinking water is not required for customers where normal occupancy is short term. A kitchen or bar sink may be used for employee water drinking facilities. Fixtures for public use as required by this section may be met by providing a centrally located facility accessible to several stores.

The maximum distance from entry to any store to this facility shall not exceed feet. The maximum distance from entry to any store from this facility shall not exceed feet. Multiple dwellings or boarding houses without public laundry rooms shall not require laundry trays. Reserved Requirements for employees and customers may be met with a single set of restrooms.

If the design number of customers in food handling establishments exceeds , separate facilities for employees and customers are required.

All showers and lavatories shall have thermostatic control and timing devices. Laboratories in higher education facilities shall have safety showers. Warehouse storage area requirements shall be permitted to be met by providing a facility centrally located within the storage area. The maximum travel distance to the facility shall not exceed feet. Showers may be omitted in recreational facilities without locker rooms when approved by the Authority Having Jurisdiction.

Fixtures, appliances and equipment shall be connected to support the weight of the device and any ad- ditional probable loads that may impact on the device. Fixtures shall be rigidly supported so that no strain is transmitted in the piping connections. Cast-iron soil pipe—at base and at each story height.

Steel threaded pipe—at every other story height. Copper tube—at each story height but not more than foot intervals. Lead pipe—four-foot intervals. Plastic pipe—see Section 8. Flexible plastic tubing—each story height and at mid-story. Stainless steel drainage pipe—at each story height. Cast-iron soil pipe—minimum of one hanger per pipe length located within 18 inches of each joint up to foot maximum pipe length , at changes in direction, and at branch connections.

Where pipe is sus- pended by non-rigid hangers more than 18 inches long, provide lateral support at foot maximum spacing. Lateral support shall consist of either 1 a sway brace or 2 either a change in direction or a branch connec- tion that provides the required lateral support. One-inch size and larger—foot intervals. Lead pipe—on continuous metal or wood strips for its entire length.

Flexible plastic tubing—32 inches. Stainless steel drainage pipe—10 foot intervals, changes of direction and branch connections. Piers shall be of concrete, brick, or other masonry construction. Provision shall be made for expansion and contraction of the piping. See Sections 4. Other piping mate- rial shall be so anchored as to support the stack at the base. Plastic drain, waste, vent, and pressure pipe shall be installed and supported as recommended by the manufacturer's instructions. Maximum horizontal support spacing shall be based on the pipe schedule or wall thickness, the pipe size, the system operating temperature, the ambient temperature, and any concentrated loads.

Vertical pipe shall be maintained in straight alignment. Intermediate supports shall be provided where required for stability. Pipe shall also be supported at changes of direction or elevation. Supports shall not compress, distort, cut, or abrade the piping and shall allow free movement. Provisions shall be made for expansion and contraction of the piping. Fixture trap arms longer than three feet shall be supported as close as possible to the trap. The spacing for vent piping shall be permitted to be based on vapor service.

Such drains shall discharge sepa- rately through an air gap or, where permitted, an air break. Fixtures and appliances used for the storage, processing, preparation, serving, dispensing, or sale of food shall be drained indirectly.

Where bar sinks, glass-washing sinks, or other counter sinks cannot be vented according to the requirements of Chapter 12, they shall be permitted to each discharge separately to a trapped and vented receptor through indirect waste pipes providing either an air break or an air gap.

Traps shall be provided in the indirect waste pipe when required under Section 9. The above requirements do not apply to refrigerated food preparation areas or work rooms. Where necessary, cleanouts shall be provided in accordance with Section 5.

Search icon An illustration of a magnifying glass. User icon An illustration of a person's head and chest. Sign up Log in. Web icon An illustration of a computer application window Wayback Machine Texts icon An illustration of an open book.

Books Video icon An illustration of two cells of a film strip. Video Audio icon An illustration of an audio speaker. Audio Software icon An illustration of a 3. While some states provide integrated codes such as the California codes and the New York City building codes, these are not available in all cases.

Where these are not provided, UpCodes has integrated the local amendments in jurisdiction like Pennsylvania and New York State. Every three years the ICC works to publish a new set of I-Codes that can be adopted and modified by each state. The Construction Codes for each jurisdiction will be selected from this set of publications. Most states follow a three-year code adoption cycle in order to keep up-to-date with the ICC revision process. The I-Codes may indicate your project is required to have a sprinkler system throughout the building.

The I-Codes do not indicate exactly how the sprinkler system must be designed. However, the I-Codes adopt NFPA 13, Standard for the Installation of Sprinkler Systems which provides you with the requirements on sprinkler head spacing, sprinkler type, location, etc.

This is also typical to other systems such as fire alarms. Every new building and even existing buildings must be designed to accommodate handicapped patrons. Therefore, it is important to determine the application of each document based on the project scope and location.

Skip to content. International Code Council The International Code Council provides free code references for a number of states, plus free access to the International Codes. Below is a list of some of the most referenced codes for architects: United States Access Board The US Access Board is a federal agency that promotes equality for the disabled. Find code adoptions by state here.



0コメント

  • 1000 / 1000